Detuned Reactors / Inductorsplaceholder · competitor · indiamart.com
Reactors & Inductors

Detuned Reactors / Inductors

7% (~189 Hz @50Hz), 14%,capacitor-step current ptypically ±3% (IEC); <=5

A detuned reactor is a three-phase inductor connected in series with each step of a power-factor-correction (PFC) capacitor bank to shift the bank's resonant frequency below the lowest significant harmonic (typically the 5th).

Overview

A detuned reactor is a three-phase inductor connected in series with each step of a power-factor-correction (PFC) capacitor bank to shift the bank's resonant frequency below the lowest significant harmonic (typically the 5th). This 'detunes' the LC circuit so the capacitors cannot resonate with system harmonics — preventing harmonic amplification, capacitor and transformer overloading, and voltage distortion in networks with high THD from non-linear loads. The detuning is set by the tuning factor (p): common values are 7% (tuned ~189 Hz at 50 Hz), 14%, and 5.67% for higher-order harmonic environments. ACE manufactures these as natural-cooled, compact, H-class dry-type reactors with high linearity (>=180% of rated current per the existing site) and low losses, designed to carry rated plus harmonic current without significant inductance drop. Buyers choose ACE to protect capacitor banks and stabilise PFC panels in harmonic-rich plants.

Specifications

Standard parameters — confirmed on enquiry
Tuning / detuning factor (p)7% (~189 Hz @50Hz), 14%, 5.67% — and as specified
Rated currentcapacitor-step current plus harmonic loading; linearity >=180% (existing site)
Inductance tolerancetypically ±3% (IEC); <=5% inductance drop up to ~1.8x nominal capacitor current
Voltage classLV (e.g. 415 / 440 / 525 / 690 V) and reactor rated voltage per step kVAr
Frequency50 Hz (60 Hz on request)
Phasesthree-phase
InsulationClass H; thermal protection (thermostat/PTC) option; low dB / low noise (existing site)
Losseslow watt-loss per kg; natural air cooled, compact (existing site)
Mountingeasy panel mounting (existing site); Enclosure: open IP00 / as specified
Applicable standardsIEC 60076-6 (reactors), IEC 61921, IEEE-519

Applications

  • Power-factor-correction (PFC) panels and capacitor banks (existing site)
  • Anti-resonance / harmonic-resonance prevention for capacitor steps (existing site)
  • Line-pollution / harmonic mitigation systems (existing site)
  • Power-loss management in industrial plants with non-linear loads (existing site)
  • Protecting capacitors, transformers and feeders from harmonic overload
Built to specification. Custom ratings, voltages and enclosures available — share your single-line diagram and duty cycle and we'll engineer the unit to match. Specifications shown are standard ranges and are confirmed against your requirement on enquiry.

Request a quote — Detuned Reactors / Inductors

Tell us your application and ratings. Our engineering team replies within one business day.